If you need a steady pressure supply with minimal energy consumption, Vega 1.5kW VSP Pump is the way to go. It has a pressure range of 2 to 6 bar and a flow rate of 16 to 108 liters per minute. When there is no flow, it has an automatic start/stop feature built in. This product is issued with a Letter Of Authority.
"*" indicates required fields
Categories: Centrifugal Pumps
Description
Features & Benefits
- Easy to operate
- Low noise level
- Automatic start/stop function
- Pre-wired with a 3-point plug
- Energy-efficient
Up to 80% more energy savings compared to traditional pump systems - Restart delay
An integral time delay for restart after 3 seconds protects the motor from heat build-up due to continuous on/off switching - Auto-rotation
A built-in timer will automatically start the pump within a pre-selected cycle to rotate the bearings - Constant pressure
A pressure transducer ensures that constant pressure is maintained even when multiple water outlets are used simultaneously - Class leading efficiency
The unit has the following integrated functions for protection from:
- Dry run
- Over-current
- Over/under voltage
- Overload
- Abnormal Pressure
Additional information
Brand | Vega |
---|
Video Guides
Troubleshooting VSP Booster Pumps
When all fixtures are shut off, the pump does not turn off.solomon@casson.co.za2023-07-28T10:40:25+02:00
- Retest after closing the valve that is directly attached to the pump’s outlet side.
- Check for leaks in the plumbing between the pump and the fixtures.
- Check the pressure in the pressure vessel after releasing all the pressure from the pump and pipeline. The pressure should be between 1.5bar and 2bar
- Check that the non-return valve on the pump is free of debris and that it is sealing properly.
The pump indicates “waterless” and does not turn on when a fixture is opened.solomon@casson.co.za2023-07-28T10:41:17+02:00
- Examine the water supply tank to see if it is or was empty. Fill the tank and press the “hand start” button to turn the pump on.
- Check that the pressure does not drop below the value of BO3 for longer than 3 minutes during normal water usage. Otherwise, adjust B03 slightly lower.
The pump continuously cycles on and off, with a delay of a few seconds or minutes in between each cycle.solomon@casson.co.za2023-07-28T10:42:24+02:00
- Check for leaks in the plumbing between the pump and the fixtures.
- Check that the non-return valve on the pump is free of debris and that it is sealing properly.
When the pump starts or runs, the circuit breaker tripssolomon@casson.co.za2023-07-28T10:43:20+02:00
- Confirm that the circuit breaker rating is correct according to the pump size.
- Look for any traces of water that could cause a short circuit in the controller/VSD or motor.
- Check all electrical connections for short circuits and exposed wires.
No lights are illuminated on the controller/VSD and the pump doesn’t turn on.solomon@casson.co.za2023-07-28T10:44:17+02:00
- Examine the electrical cable, electrical connections and protection equipment between the power supply and controller/VSD.
- Ensure that other electrical equipment turns on when plugged into the same outlet as the pump.
The controller/VSD displays E01solomon@casson.co.za2023-07-28T10:45:18+02:00
- Check the power supply to the controller/VSD for low voltage conditions.
- Test the voltage between the neutral and earth terminals. This voltage should be less than 23V
The controller/VSD displays E03solomon@casson.co.za2023-07-28T10:46:23+02:00
Examine the pressure transducer and the electrical cable between the pressure transducer and the controller/VSD for any damage.
The controller/VSD displays E04solomon@casson.co.za2023-07-28T10:47:28+02:00
- Check to see if the motor or aluminium backside of the controller/VSD is hot.
- Ensure that the motor and controller/VSD has adequate ventilation.
When the pump should start, the controller/VSD displays E08 and the motor doesn’t turn.solomon@casson.co.za2023-07-28T10:48:05+02:00
Ensure that the motor turns freely by hand after the power has been switched off.